Weshine® the CT PT Analyzer invented for Potential Transformer Testing is a new product created after widely adopting the suggestions of customers and in-depth theoretical research. It is based on the widely acclaimed and applied automatic FA series transformer integrated tester produced by our company. Using high-performance DSP and arm, advanced manufacturing technology ensures stable and reliable product performance, complete functions, high degree of automation, high efficiency, which is at the leading level in China. It is a professional testing equipment industry for instrument transformer testing.
Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.
Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.
In accordance with the transformer types and levels of automatic choose which standard test.
Based on advanced principle of low-frequency test method that can meet the CT test on knee voltage up to 30 kV.
The instrument can store 2000 groups of test data that won’t be lost when power off. After test ended, the data can be coped to PC by USB disk for analysis and being transformed into WORD report.
Test is simple and convenient, one-click can complete tests of CT secondary resistance, excitation, ratio and olarity.
Easy to carry, because the weight is less than 9 kg.
Name |
CT PT Analyzer for Potential Transformer Testing |
|
Usage |
Class P/TP CT & VT |
|
Output |
0~180Vrms,12Arms,18A(peak value) |
|
CT Ratio |
Range |
1~30000 |
accuracy |
±0.05% |
|
PT Ratio |
Range |
1~30000 |
accuracy |
±0.05% |
|
Phase |
Range |
±5min |
accuracy |
0.5min |
|
DC resistance |
Range |
0~300Ω |
accuracy |
2%±2mΩ |
|
Burden |
Range |
0~300VA |
accuracy |
2%±0.2VA |
|
Power supply |
AC220V±10%,50Hz |
|
Environmental Conditions |
Operating temperature :-10οC ~50οC,Humidity :≤90% |
|
Weight and Dimensions |
Dimensions:340 mm×300 mm×150mm,Weight<9kg |
parameters |
description |
P |
TPY |
measure |
PR |
PX |
TPS |
TPX |
TPZ |
|
rated primary current |
Used to calculate the ratio of actual current accurately |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
|
rated burden |
Rated load of plate, power factor for 0.8 or 1 |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
|
power factor |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
||
Rated accurate limit coefficientKalf |
The provisions of the plate,default 10,used to calculate the limit e.m.f. and their corresponding composite error |
√ |
|
|
|
|
|
|
|
|
Rated symmetric short-circuit current coefficientKssc |
The provisions of the plate,default 10,used to calculate the peak and their corresponding limits e.m.f transient error |
|
√ |
|
|
|
√ |
√ |
√ |
|
Primary time constant |
default :100ms |
|
√ |
|
|
|
|
√ |
√ |
|
Second time constant |
default :3000ms |
|
√ |
|
|
|
|
|
√ |
|
Duty cycle |
C-t1-O or C-t1-O-tfr-C-t2-O,default:C-t1-O cycle |
|
√ |
|
|
|
|
√ |
|
|
t1 |
Current time limit for the first time,default:100ms |
|
√ |
|
|
|
|
√ |
|
|
tal1 |
Time required to reach the specified accuracy during the first magnetization cycle,default:40ms |
|
|
|
|
|
|
|
|
|
tfr |
Time required to reach the specified accuracy during the second magnetization cycle,default:500ms,Choose C-t1-O-tfr-C-t2-O,Cycle will be shown |
|
√ |
|
|
|
|
√ |
|
|
t2 |
Current time limit for the second time,default:100ms.Choose C-t1-O-tfr-C-t2-O,Cycle will be shown |
|
√ |
|
√ |
|
|
√ |
|
|
tal2 |
Second the flow by maintaining accurate limits of time,default:40ms |
|
√ |
|
|
|
|
√ |
|
|
choose C-t1-O-tfr-C-t2-O,cycle will be shown |
||||||||||
Rated instrument security coefficient FS |
Nameplate regulation,default:10 |
|
|
√ |
|
|
|
|
|
|
Used for calculation of the limit of composite error and their corresponding electromotive force |
||||||||||
Rated calculating coefficients |
|
|
|
|
|
√ |
|
|
|
|
Rated inflection point potential(Ek) |
|
|
|
|
|
√ |
|
|
|
|
Ie corresponding with Ek |
|
|
|
|
|
√ |
|
|
|
|
dimensioning factor |
|
|
|
|
|
|
√ |
|
|
|
Rated Ual |
The rated equivalent quadratic limit voltage |
|
|
|
|
|
√ |
|
|
|
Ial corresponding with Ual |
|
|
|
|
|
|
√ |
|
|
experiment item |
Description |
Connection diagram |
||
resistance |
excitation |
ratio |
||
√ |
|
|
Measure CT’s secondary winding resistance |
Fig 2.10,must disconnection if measuring primary winding. |
√ |
√ |
|
Measure CT’s secondary winding resistance and excitation characteristic |
Fig 2.10,must disconnection if measuring primary winding. |
|
|
√ |
Check it’s ratio and polarity |
Fig 2.11 |
Weshine has 8 years experience specifically for deal with complete range of Electrical Equipment. At present, Weshine has invented various CT PT Analyzer for Potential Transformer Testing as shown as form:
ORDERING INFORMATION FOR CT PTANALYZER FOR Potential Transformer Testing |
|||||
Cat. No. |
Max Test Voltage |
Max Test Current |
Ratio Test Accuracy |
Dimensions |
Weight |
VS-2800 |
0 to 2500 Vrms |
0 to 1000 A |
±0.2% |
425 x 290 x 310 mm |
30 kg |
VS-2800A |
0 to 180 Vrms |
0 to 150 A |
±0.1% |
340 x 300 x 150 mm |
9 kg |
VS-2800B |
0 to 180 Vrms |
0 to 150 A |
±0.05% |
340 x 300 x 150 mm |
9 kg |
*Based on Supply Chain issues: Please contact your preferred Authorized Weshine Distributor for current pricing and lead times.
HOW TO CHOOSE CT PT ANALYZER FOR Potential Transformer Testing? ■VS-2800: True power frequency, simulates the working state of the transformer. ■VS-2800A: Upgraded on the basis of VS-2800, using frequency conversion technology, compact body, strong anti-interference ability, lower test voltage means safer and more reliable. ■VS-2800B: Unmatched turns ratio test accuracy reached 0.05%, small innovation, big wisdom. |
We always believe that all the success of our company is directly related to the quality of the products we provide. CT PT Analyzer for Potential Transformer Testing meet the highest quality requirements specified in ISO9001, ISO14000:14001 guidelines and our strict quality control system.
For further information on Weshine's Service Solutions, contact our 24/7 online sales representative to get quotes from Weshine.